We just upgraded to a double blower and was wondering how members ran power supply for their blowers.  We have have an older barn with some old wiring.  We put in a new panel and will run new wire as well.  Thanks in advance.
 

GoWyo

Well-known member
Joined
Nov 29, 2008
Messages
1,691
Location
Wyoming
Run two 20 amp circuits to separate 20 amp outlets.  I put ours side by side in a double outlet box.
 

renegadelivestock

Well-known member
Joined
Mar 12, 2010
Messages
324
GoWyo said:
Run two 20 amp circuits to separate 20 amp outlets.  I put ours side by side in a double outlet box.

I run mine on a similar system, but I used 30 amp breakers, I found the 30 amps to be more effective when working large numbers of cattle
 

GoWyo

Well-known member
Joined
Nov 29, 2008
Messages
1,691
Location
Wyoming
Make sure your wire size is big enough for the 30 amps with the length of run from the panel.
 

J2F

Well-known member
Joined
Nov 28, 2011
Messages
258
FYI  May want to check with your local electrician (or insurance company) on putting a 20 amp rated outlet on a 30amp circuit.
 

J2F

Well-known member
Joined
Nov 28, 2011
Messages
258
J2F said:
FYI  May want to check with your local electrician (or insurance company) on putting a 20 amp rated outlet on a 30amp circuit.

copper #10
 

renegadelivestock

Well-known member
Joined
Mar 12, 2010
Messages
324
just to clarify, I did have the dedicated circuits put in by a licensed electrician, i'm no expert on these things, so I left it up to someone who IS! lol
 

obie105

Well-known member
Joined
Oct 17, 2011
Messages
780
I believe if your barn is insured and in case of fire it has to be to code. I am very lucky my Dad and brother are both electricians and we can run about anything you can imagine all at once.
 

jd438

Well-known member
Joined
Oct 13, 2010
Messages
61
Well it's a pretty long run from the panel, so we are going with 2 20 amp breakers and will run 10 gauge wire to 20 amp outlets. 
 

Bryce.mulder

New member
Joined
Jun 29, 2019
Messages
2
Can a 1.5 inch hose with a double blower nozzle work for a double blower? Or do I have to have a 2 inch hose with the double blower nozzle? Will a 1.5 inch hose with the standard nozzle hurt a double blower?
 